CS 20-H by Van der Heijden
Chiller / Recirculating Cooler
Performance Characteristics
The CS chillers expand the Huber product range with compact and highly affordable recirculating coolers. CS chillers combine cool and smart technology in one unit. For many applications, recirculating coolers further reduce water consumption and lower the operating costs. The investment pays itself off after a short time because of the water savings and the low purchase price. All the models are air-cooled and equipped with bypass, manometer and sensor to monitor the flow. The devices are characterized by the fact that they are easy to operate and maintenance-free. In addition, they have a low-noise construction and fan for quiet operation. Furthermore, the CS chillers are particularly suited for constant temperature control for laboratory applications, e.g. for cooling vacuum pumps, rotary evaporators, electron microscopy, AAS-devices, ICP-devices, extraction, distillation and many more.
Functions overview
- High efficiency
- Precise temperature control
- Environmentally-friendly, economic cooling solution
- Low operating costs
- Reduced water consumption
- Powerful recirculation pump
- Extremely quiet and simple operation
- Low-noise construction
Product impressions
Controller
The controller is particularly convincing with its simple operating unit and its multilingual menu navigation. The menu shows understandable text descriptions of warnings or fault conditions. In addition, the controller offers capacitive touch technique with acoustic confirmation. It has a bright O-LED display and an easy care and hygienic operating area.
Read moreTemperature range | -20...85 |
Temperature stability | ±0,5 |
Safety class | I / NFL |
Protection class | IP52 |
Dimensions (W x D x H) | 580 x 660 x 820 mm |
Weight, net | 115 kg |
Heating capacity | 1 | ||||||||||||
Cooling capacity |
|
||||||||||||
Refrigeration machine | air-cooled, CFC- and HCFC-free | ||||||||||||
Refrigerant 1st stage | R-449A (A1, H280) | ||||||||||||
Refrigerant quantity 1st stage | 1,1 kg |
Delivery capacity pressure pump max. | 10 l/min; 3,5 |
Pump connection | G3/8 AG male |
Interface digital | RS232 |
Permissible ambient temperature | 5...32 °C |
Sound pressure level | 57 |
Bath volume | 37 |
Filling volume min. | 24 |
Power supply | 230V 1~ 50Hz |
Current consumption max. | 13 |
Fuse | 16 A |
Please take further technical information as well as information about the scope of delivery, accessories and peripheral devices from the PDF data sheet. In cases of doubt the details given in there apply. If nothing to the contrary is quoted then the performance data referred is at an ambient temperature of 20°C.
Please observe the notes on installation and/or the space requirements of our products.
The following voltage and frequency tolerances apply based on EN60034-1:
Voltage +/- 5% for a frequency tolerance at the same time of +/- 2%
Examples to illustrate this: Not permissible, for example. is -5% on the voltage and +2% on the frequency. Permissible, on the other hand, are tolerances of -5% on the voltage and -2% on the frequency.
We reserve the right to make technical changes and correct errors. Illustrations can deviate from the original.