Unichiller P025w OLÉ

Unichiller P025w OLÉ

Chiller / Recirculating Cooler

Model: Unichiller P025w OLÉ Group: 3 Order No.: 3052.0024.98 E-class: 32-09-01-18
Request now

Performance Characteristics

Huber Unichillers offer better efficiency, stable pressure and delivery performance with a constant cooling water temperature compared to traditional tap water cooling. Chillers also reduce water consumption and help conserve the environment whilst lowering operating costs. Unichillers are suitable for the removal of heat from chemical processes, cooling technical plants or as a central cooling water supply for laboratories. All Unichillers are designed for continual operation at ambient temperatures up to +40°C. Installation in an outside areas is possible with optional weather protection and winter operation packages. Pumps are available with an extended pressure and flow rate for applications with a high pressure drops.

Functions overview

  • Environmentally-friendly, economic cooling solution
  • High efficiency
  • Precise temperature control
  • Simple operation with menu navigation
  • Robust stainless construction
  • Reliable continuously operation with warning functions
  • Easy to fill and empty
  • Adjustable bypass, level indicator with sight glass and digital manometer
  • Bright, large OLED display
  • USB and RS232 interfaces

Product impressions

Controller

The new OLÉ controller combines state-of-the-art technology with simple operation. OLÉ models are suitable for routine tasks in research and industry and are convincing as practice oriented basic equipment. Option: Pt100 sensor connection #10519 to display (not control) e.g. of the process temperature (only available factory fitted, additional charge).

Read more

Temperature range -10...40
Temperature stability ±0,5
Temperature display OLED Display
Display resolution 0,1 K
Alarm message optic, acoustic
Controller OLÉ
Safety class I / NFL
Protection class IP20
Dimensions (W x D x H) 420 x 487 x 579 mm
Weight, net 63 kg

Cooling capacity
15 2,5
0 2
-10 1,2

°C

kW

Refrigeration machine water-cooled, CFC- and HCFC-free
Refrigerant 1st stage R-449A (A1, H280)
Refrigerant quantity 1st stage 0,4 kg

Delivery capacity pressure pump max. 25 l/min; 2,5
Pump connection G3/4 AG male
Pump speed adjustable no
Pump type B
Pump characteristics Pressure pump, speed not variable, manual bypass integrated

Interface digital USB (Device), RS232 Interface

Permissible ambient temperature 5...40 °C
Sound pressure level 60
Filling volume min. 3,8
Expansion volume 1,7
Cooling water connection G1/2 male
Cooling water consumption at 15°C, flow -10°C 72
Cooling water consumption at 15°C, flow 0°C 84 l/h
Cooling water consumption at 15°C, flow 15°C 84
Cooling water differential pressure min. 3 bar
Cooling water pressure max. 6 bar
Power supply 220-240V 1~/2~ 50Hz
Current consumption max. 9,5

Please take further technical information as well as information about the scope of delivery, accessories and peripheral devices from the PDF data sheet. In cases of doubt the details given in there apply. If nothing to the contrary is quoted then the performance data referred is at an ambient temperature of 20°C.

Please observe the notes on installation and/or the space requirements of our products.

The following voltage and frequency tolerances apply based on EN60034-1:
Voltage +/- 5% for a frequency tolerance at the same time of +/- 2%

Examples to illustrate this: Not permissible, for example. is -5% on the voltage and +2% on the frequency. Permissible, on the other hand, are tolerances of -5% on the voltage and -2% on the frequency.

We reserve the right to make technical changes and correct errors. Illustrations can deviate from the original.

Quotation request & Warranty

Are you interested in this product or would you like to take advantage of the free extended warranty? Please feel free to contact us.

Request a quoteExtend warranty