Unichiller 022w-H

Unichiller 022w-H

Chiller / Recirculating Cooler

Model: Unichiller 022w-H Group: 3 Order No.: 3010.0122.01 E-class: 32-09-01-18
Request now

Performance Characteristics

Huber Unichillers offer better efficiency, stable pressure and delivery performance with a constant cooling water temperature compared to traditional tap water cooling. Chillers also reduce water consumption and help conserve the environment whilst lowering operating costs. Unichillers are suitable for the removal of heat from chemical processes, cooling technical plants or as a central cooling water supply for laboratories. All Unichillers are designed for continual operation at ambient temperatures up to +40°C. Installation in an outside areas is possible with optional weather protection and winter operation packages. Pumps are available with an extended pressure and flow rate for applications with a high pressure drops.

Functions overview

  • Environmentally-friendly, economic cooling solution
  • High efficiency
  • Precise temperature control
  • Powerful circulation pump
  • Robust stainless construction
  • Reliable continuously operation with warning functions
  • Easy to fill and empty
  • Illuminated filling level indicator
  • Pilot ONE controller with 5.7" touchscreen
  • 2 x USB (Host and Device), Ethernet and RS232 interfaces

Product impressions

Controller

The new multi-touch controller Pilot ONE offers a brilliant 5.7" touchscreen with graphic functions and a comfortable navigation menu. All important operating parameters and temperature values are neatly displayed on the touchscreen. Thanks to the new favourites menu, the one-click operation and the integrated technical glossary the operation is very easy, just like on a smartphone. Integrated USB and Ethernet ports allows connection to a PC or network, e.g. for remote control or data transmission.

Read more

Temperature range -10...100
Temperature stability ±0,2
Controller Pilot ONE
Safety class III / FL
Protection class IP20
Dimensions (W x D x H) 420 x 487 x 579 mm
Weight, net 61 kg

Heating capacity 1,8 - 2,1
Cooling capacity
15 2,2
0 1,6
-10 1

°C

kW

Refrigeration machine water-cooled, CFC- and HCFC-free
Refrigerant 1st stage R-449A (A1, H280)
Refrigerant quantity 1st stage 0,43 kg

Delivery capacity pressure pump max. 29 l/min; 1
Pump connection G3/4 AG male
Pump speed adjustable Yes
Pump type Immersion pump
Pump characteristics Pressure pump, variable speed

External sensor connection Pt100
Interface digital Ethernet, USB (Host u. Device), RS232

Permissible ambient temperature 5...40 °C
Sound pressure level 60
Filling volume min. 3,8
Expansion volume 1,7
Cooling water connection G1/2 male
Cooling water consumption at 15°C, flow -10°C 77
Cooling water consumption at 15°C, flow 0°C 96 l/h
Cooling water consumption at 15°C, flow 15°C 95
Cooling water differential pressure min. 3 bar
Cooling water pressure max. 6 bar
Power supply 220-240V 1~/2~ 50Hz
Current consumption max. 15
Fuse 16 A

Please take further technical information as well as information about the scope of delivery, accessories and peripheral devices from the PDF data sheet. In cases of doubt the details given in there apply. If nothing to the contrary is quoted then the performance data referred is at an ambient temperature of 20°C.

Please observe the notes on installation and/or the space requirements of our products.

The following voltage and frequency tolerances apply based on EN60034-1:
Voltage +/- 5% for a frequency tolerance at the same time of +/- 2%

Examples to illustrate this: Not permissible, for example. is -5% on the voltage and +2% on the frequency. Permissible, on the other hand, are tolerances of -5% on the voltage and -2% on the frequency.

We reserve the right to make technical changes and correct errors. Illustrations can deviate from the original.

Quotation request & Warranty

Are you interested in this product or would you like to take advantage of the free extended warranty? Please feel free to contact us.

Request a quoteExtend warranty